Description (CNA)
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x includes the functionality of setting a password that is required to execute privileged commands. The password value passed to ISaGRAF Runtime is the result of encryption performed with a fixed key value using the tiny encryption algorithm (TEA) on an entered or saved password. A remote, unauthenticated attacker could pass their own encrypted password to the ISaGRAF 5 Runtime, which may result in information disclosure on the device.
Affected (CNA)
| Vendor / product | Versions |
|---|---|
| Rockwell Automation / ISaGRAF Runtime | affected 4.x; affected 5.x |
CWE
CWE-321
References
- https://www.cisa.gov/uscert/ics/advisories/icsa-20-280-01
- https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1131699
- https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-159-04
- https://www.xylem.com/siteassets/about-xylem/cybersecurity/advisories/xylem-multismart-rockwell-isagraf.pdf
ADP enrichment
No English description supplied.
- https://www.cisa.gov/uscert/ics/advisories/icsa-20-280-01
- https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1131699
- https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-159-04
- https://www.xylem.com/siteassets/about-xylem/cybersecurity/advisories/xylem-multismart-rockwell-isagraf.pdf
No English description supplied.
No references supplied.