← CVE Intelligence

CVE-2021-31884

Siemens / APOGEE MBC (PPC) (BACnet) PUBLISHED

Description (CNA)

A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.4), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.19), APOGEE PXC Modular (BACnet) (All versions < V3.5.4), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.19), Capital VSTAR (All versions with enabled Ethernet options), Desigo PXC00-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC00-U (All versions >= V2.3 and < V6.30.016), Desigo PXC001-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC100-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC12-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC128-U (All versions >= V2.3 and < V6.30.016), Desigo PXC200-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC36.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC50-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC64-U (All versions >= V2.3 and < V6.30.016), Desigo PXM20-E (All versions >= V2.3 and < V6.30.016), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus Source Code (All versions), TALON TC Compact (BACnet) (All versions < V3.5.4), TALON TC Modular (BACnet) (All versions < V3.5.4). The DHCP client application assumes that the data supplied with the “Hostname” DHCP option is NULL terminated. In cases when global hostname variable is not defined, this may lead to Out-of-bound reads, writes, and Denial-of-service conditions. (FSMD-2021-0014)

Affected (CNA)

Vendor / productVersions
Siemens / APOGEE MBC (PPC) (BACnet)affected All versions
Siemens / APOGEE MBC (PPC) (P2 Ethernet)affected All versions
Siemens / APOGEE MEC (PPC) (BACnet)affected All versions
Siemens / APOGEE MEC (PPC) (P2 Ethernet)affected All versions
Siemens / APOGEE PXC Compact (BACnet)affected All versions < V3.5.4
Siemens / APOGEE PXC Compact (P2 Ethernet)affected All versions < V2.8.19
Siemens / APOGEE PXC Modular (BACnet)affected All versions < V3.5.4
Siemens / APOGEE PXC Modular (P2 Ethernet)affected All versions < V2.8.19
Siemens / Capital VSTARaffected All versions with enabled Ethernet options
Siemens / Desigo PXC00-E.Daffected All versions >= V2.3 and < V6.30.016
Siemens / Desigo PXC00-Uaffected All versions >= V2.3 and < V6.30.016
Siemens / Desigo PXC001-E.Daffected All versions >= V2.3 and < V6.30.016
Siemens / Desigo PXC100-E.Daffected All versions >= V2.3 and < V6.30.016
Siemens / Desigo PXC12-E.Daffected All versions >= V2.3 and < V6.30.016
Siemens / Desigo PXC128-Uaffected All versions >= V2.3 and < V6.30.016
Siemens / Desigo PXC200-E.Daffected All versions >= V2.3 and < V6.30.016
Siemens / Desigo PXC22-E.Daffected All versions >= V2.3 and < V6.30.016
Siemens / Desigo PXC22.1-E.Daffected All versions >= V2.3 and < V6.30.016
Siemens / Desigo PXC36.1-E.Daffected All versions >= V2.3 and < V6.30.016
Siemens / Desigo PXC50-E.Daffected All versions >= V2.3 and < V6.30.016
Siemens / Desigo PXC64-Uaffected All versions >= V2.3 and < V6.30.016
Siemens / Desigo PXM20-Eaffected All versions >= V2.3 and < V6.30.016
Siemens / Nucleus NETaffected All versions
Siemens / Nucleus ReadyStart V3affected All versions < V2017.02.4
Siemens / Nucleus Source Codeaffected All versions
Siemens / TALON TC Compact (BACnet)affected All versions < V3.5.4
Siemens / TALON TC Modular (BACnet)affected All versions < V3.5.4

CWE

CWE-170

References

ADP enrichment

CVE

No English description supplied.