Description (CNA)
A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.
Affected (CNA)
| Vendor / product | Versions |
|---|---|
| Hitachi Energy / RTU500 series | affected RTU500 series CMU Firmware version 13.3.1; affected RTU500 series CMU Firmware version 13.3.2; unaffected RTU500 series CMU Firmware version 13.3.3; unaffected RTU500 series CMU Firmware version 13.4.1 |
CWE
CWE-787
References
ADP enrichment
No English description supplied.
No English description supplied.
No references supplied.