Description (CNA)
In multiple Codesys products in multiple versions, after successful authentication as a user, specially crafted network communication requests can utilize the CmpApp component to download files with any file extensions to the controller. In contrast to the regular file download via CmpFileTransfer, no filtering of certain file types is performed here. As a result, the integrity of the CODESYS control runtime system may be compromised by the files loaded onto the controller.
Affected (CNA)
| Vendor / product | Versions |
|---|---|
| CODESYS / CODESYS Control for BeagleBone SL | affected 0 before V4.10.0.0 |
| CODESYS / CODESYS Control for emPC-A/iMX6 SL | affected 0 before V4.10.0.0 |
| CODESYS / CODESYS Control for IOT2000 SL | affected 0 before V4.10.0.0 |
| CODESYS / CODESYS Control for Linux SL | affected 0 before V4.10.0.0 |
| CODESYS / CODESYS Control for PFC100 SL | affected 0 before V4.10.0.0 |
| CODESYS / CODESYS Control for PFC200 SL | affected 0 before V4.10.0.0 |
| CODESYS / CODESYS Control for PLCnext SL | affected 0 before V4.10.0.0 |
| CODESYS / CODESYS Control for Raspberry Pi SL | affected 0 before V4.10.0.0 |
| CODESYS / CODESYS Control for WAGO Touch Panels 600 SL | affected 0 before V4.10.0.0 |
| CODESYS / CODESYS Control RTE (for Beckhoff CX) SL | affected 0 before V3.5.19.20 |
| CODESYS / CODESYS Control RTE (SL) | affected 0 before V3.5.19.20 |
| CODESYS / CODESYS Control Runtime System Toolkit | affected 0 before V3.5.19.20 |
| CODESYS / CODESYS Control Win (SL) | affected 0 before V3.5.19.20 |
| CODESYS / CODESYS Development System V3 | affected 0 before V3.5.19.20 |
| CODESYS / CODESYS HMI (SL) | affected 0 before V3.5.19.20 |
| CODESYS / CODESYS Safety SIL2 Runtime Toolkit | affected 0 before V3.5.19.20 |
CWE
CWE-552
References
ADP enrichment
No English description supplied.
No English description supplied.
No references supplied.