Siemens / SIMATIC ET 200AL IM 157-1 PN PUBLISHED

Description (CNA)

A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0 < V4.2.5), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state. This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.

Affected (CNA)

Vendor / productVersions
Siemens / SIMATIC ET 200AL IM 157-1 PNaffected 0 before *
Siemens / SIMATIC ET 200MP IM 155-5 PN HFaffected V4.2.0 before *
Siemens / SIMATIC ET 200SP IM 155-6 MF HFaffected 0 before *
Siemens / SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants)affected 0 before V1.3
Siemens / SIMATIC ET 200SP IM 155-6 PN R1affected 0 before V6.0.1
Siemens / SIMATIC ET 200SP IM 155-6 PN/2 HFaffected V4.2.0 before V4.2.5
Siemens / SIMATIC ET 200SP IM 155-6 PN/3 HFaffected 0 before V4.2.2
Siemens / SIMATIC PN/MF Coupleraffected 0 before *
Siemens / SIMATIC PN/PN Coupleraffected 0 before V6.0.0
Siemens / SIPLUS ET 200MP IM 155-5 PN HFaffected V4.2.0 before *
Siemens / SIPLUS ET 200MP IM 155-5 PN HFaffected V4.2.0 before *
Siemens / SIPLUS ET 200MP IM 155-5 PN HF T1 RAILaffected V4.2.0 before *
Siemens / SIPLUS ET 200SP IM 155-6 PN HFaffected V4.2.0 before V4.2.5
Siemens / SIPLUS ET 200SP IM 155-6 PN HFaffected V4.2.0 before V4.2.5
Siemens / SIPLUS ET 200SP IM 155-6 PN HF T1 RAILaffected V4.2.0 before V4.2.5
Siemens / SIPLUS ET 200SP IM 155-6 PN HF TX RAILaffected V4.2.0 before V4.2.5
Siemens / SIPLUS NET PN/PN Coupleraffected 0 before V6.0.0

CWE

CWE-400