Rockwell Automation FLEX 5000 I/O - Module Fault PUBLISHED

Description (CNA)

A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IF8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.

Affected (CNA)

Vendor / productVersions
Rockwell Automation / FLEX 5000 I/Oaffected Version 2.011 or below

CWE

CWE-1287

References

ADP enrichment

CISA-ADP

No English description supplied.